29 April 2011

Solid Waste Disposal: planning requirements & equipment


PAUL HAY Capital Projects

  

Solid Waste Disposal

Author:          Paul Hay
e-mail:             paul.hay@phcjam.com
profile:            www.linkedin.com/in/phcjam



1.0         SOLID WASTE DISPOSAL USES ENERGY AND SPACE

1.1            Energy is first used to package and transport goods then to collect them as trash.

1.2       Trash compactors also have energy and space requirements.

1.3       Provision for the delivery of supplies, collection and storage of solid waste can (a) require more space than other disposal systems; (b) present a fire hazard; and (c) can create serious local environmental problems.

1.4       Solid Waste is considered as either Ahigh grade@ or Alow grade@ resources: the former being recyclable and the latter fuel for incineration.
1.4.1    High grade resources include aluminum, steel, paper, cardboard and some plastics;
1.4.2    Incineration of low grade resources may cause air pollution and ash-disposal problems.
1.4.3    Low grade resources should be kept clean and dry before burning.

1.5       The earlier resources are separated the less energy will be used.

1.6       Recycling saves energy.
1.6.1    50% less energy is used to produce cardboard from recycled material;
1.6.2    52% less to recycle steel; and
1.6.3    96% less to recycle aluminum.

1.7       Anaerobic combustion in enclosed land-fills will generate methane gas after many years, and this can be used to support generation of electricity and co-generation: where heat is recovered from the generating process.


2.0         DISPOSAL OF RESIDENTIAL WASTE SHOULD BE PLANNED

2.1       Solid waste should be stored in well ventilated spaces.

2.2       The Kitchen is generally the location for storage of solid waste in residences.

2.3       A better location for storage of residential waste is in a room entered from the Kitchen and opening to the outdoors.

2.4       Garbage disposal units grind organic food scraps and dispose of them into the central sewer where they are better able to bio-degrade than in landfills.
2.4.1    Water and energy are used in the process.
2.4.2    The central sewers also require more energy to treat the increased flow.
2.4.3    Moisture is reduced in garbage receptacles which keeps waste in a better condition for incineration; and
2.4.4    Weight of garbage is reduced in the process.

2.5       Garbage compactors are not necessarily advantageous.



3.0       DISPOSAL OF WASTE NEEDS TO BE FACILITATED IN LARGE BUILDINGS

3.1       Industrial and commercial processes generate waste of all types: some being toxic.

3.2       Collection of waste is a three stage process.
3.2.1    Waste generated at work stations are initially placed in bins provided.
3.2.2    Bins are emptied into collection carts which are stored in service closets until full;
3.2.3    These closets have service sinks to wash the bins; and
3.2.4    In the final stage, trash is transported to the ground floor via service elevator for further storage and processing.

3.3       Storage spaces need to be cool, dry and well ventilated.
3.3.1    Burnable trash can be shredded and incinerated.
3.3.2    A sprinkler system is advisable; but
3.3.3    Regulations may limit use of incinerators.

3.4       The garbage is finally collected and transported away from the building.


Figure showing Stages for Collection of Waste

Fig. 1: Stages for Collection of Waste [Source:- Mechanical & Electrical Equipment for Buildings]




4.0         SPECIALIZED EQUIPMENT MAY BE USED



4.1       Incineration reduces waste transported to landfill.

4.2       Modern incinerators produce less pollution and facilitates heat recovery.
4.2.1    Hot water or steam is produced.
4.2.2    In large-scale operations, steam produced can be used to generate electricity.  
  
4.3       Garbage can be compacted and bagged.

4.4       Compactors can reduce the volume of trash by 90%.
4.4.1    Compactors need to be vibration-isolated.
4.4.2    Some compactors are manually free standing and others automatic chute-fed.
4.4.3    Many have built-in sprays for fire control and disinfection.
4.4.4    Access to water and floor drains is desirable.

4.5       Pulping systems (a) reduce air pollution that may result from use of incinerators, and (b) reduce space needed for storage.
4.5.1    Water is introduced and waste ground into pulp.
4.5.2    90% of water is extracted by a water press to leave a transportable slurry.
4.5.3    The volume of waste is reduced by 20%.
4.5.4    Extracted water is re-used.
4.5.5    Pulping systems should not be used for metals or plastics.

4.6       Vacuum systems use a grinder and evacuation tube.
4.6.1    Air is used as the medium for transportation.
4.6.2    Lines are small and waste can be moved horizontally or upwards.

Figure showing Pulping System

Fig. 2:  Pulping System [Source:- Mechanical & Electrical Equipment for Buildings]



FURTHER READING

            Mechanical and Electrical Equipment for Buildings, 8th edition, Benjamin Stein, John S. Reynolds, John Wiley & Sons Inc., USA, 1992

Conveyance Systems: escalators, elevators, etc.



PAUL HAY Capital Projects


Conveyance Systems

Author:          Paul Hay
e-mail:            paul.hay@phcjam.com
profile:           www.linkedin.com/in/phcjam


1.0   MECHANICAL DEVICES MOVE PEOPLE & FREIGHT

1.1_      Moving Walks and ramps are used to (a) assist in walking long distances, (b) transport large and bulky objects, and (c) reduce congestion:
1.1.1   Inclines up to 15E can be provided;
1.1.2   Maximum allowable speeds depend on the inclination and design approaches.

1.2       Pneumatic tubes transport cylinders containing paperwork, money, etc. from one end of a tube to another:
1.2.1   Sizes range from 50 mm diameter to 150 mm x 450 mm (for x-rays);
1.2.2   Air pressure propels the cylinders through the tubes; and
1.2.3   Complex systems use computers to deliver cylinders to pre-selected locations along the tube.

1.3       Endless belt conveyors carry paperwork horizontally in packs or vertically in slots.



Conveyor System



Figure 1: Conveyor System

[Source:- AIA Architectural Graphics Standards]


1.4       Trays and dumbwaiters carry paperwork, food, etc. between departments in large commercial buildings or between floors of multi-storey buildings:
            1.4.1   Tray systems automatically transport trays via moving carriers between dispatch cut-outs at intervals along a chain;
1.4.2   Dumbwaiters use ropes and pulleys to transport items on cars or platforms through a vertical shaft:
1.4.2.1            They can be manual or automatic;
1.4.2.2            Manual operation is limited to two floors;
1.4.2.3            They are used in restaurants, libraries, and offices;
1.4.2.4            Vertical shafts should be installed adjacent to other vertical shafts.

1.5       An escalator is a mechanical staircase with moving treads which transport standing pedestrians.

1.6       Elevators can be electric traction or hydraulic.

2.0   ESCALATORS ARE MORE EFFICIENT THAN ELEVATORS

Escalator

Fig. 2: Escalator

[Source:- Mechanical & Electrical Equipment for Buildings]


2.1       Escalators occupy a fifth of the space elevators require to transport comparable amounts of people.

2.2       A sixth less escalators are required to move comparable amounts of people.

2.3       Escalators are typically 800 mm or 1,000 mm wide between handrails.

Escalator in crisscross arrangement



Figure 3: Escalator in crisscross arrangement

[Source:- Mechanical & Electrical Equipment in Buildings]

2.4       They are usually installed in pairs:
2.4.1   They can be installed in parallel or criss-cross;
2.4.2   Treads and handrails are inclined at 30E from the lower floor;
2.4.3   50 m2 space should be provided at either end of the escalator to facilitate easy mounting and dismounting.


Escalator in parallel arrangement



Figure 4: Escalator in parallel arrangement

[Source:- Mechanical & Electrical Equipment in Buildings]

2.5       Escalators can serve up to 5 storeys.

2.6       Escalators are constructed as a steel-trussed framework:
2.6.1   Motor-driven sprocket wheels at each end revolve to form two chains which pull a conveyor-belt of treads;
2.6.2   Sprocket wheels and chains also move the handrails;
2.6.3   Automatic roller shutters can be deployed over tops of horizontal wellway openings for fire protection on any floor:
2.6.3.1            Sprinklers can be installed on the soffit of the escalators and on the ceiling immediately surrounding the wellway;
2.6.3.2            Blowers on the roof can force fresh air through floor openings; and
2.6.3.3Extractors can exhaust indoor air above the roof.


3.0         DESIGN FOR ELEVATORS INVOLVE THEIR LOBBIES AND CABS

Elevator Lobbies


Figure 5: Elevator Lobbies

[Source:- AIA Architectural Graphics Standards]

3.1       Double-decker cabs require escalators to transport people from the ground floor to the upper floor.

3.2       Sky lobbies require the building to be divided into 2 or 3 zones:
3.2.1   Each zone has independent elevator systems using a common shaft;
3.2.2   Express elevators facilitate movement between lobby zones.

3.3       Clear opening for commercial installations is typically 1,050 mm.

3.4       Clear opening up to 1,500 mm wide are available for service elevators and hospitals.

3.5       Centre-opening doors provide the fastest closing speeds.

3.6       Emergency power is recommended as brakes hold cabs stationery during power outages or brown-outs:
3.6.1   Hydraulic elevators and small traction cabs can be lowered manually; but
3.6.2   Emergency power is critical for large cabs, especially express elevators.


Traction & Hydraulic Elevators


Figure 6: Traction & Hydraulic Elevators

[Source:- AIA Architectural Graphic Standards]



4.0   TRACTION ELEVATORS ARE MORE ECONOMICAL TO OPERATE

4.1       Mechanical components include (a) grooved sheave, (b) electric motor with brakes, (c) auxiliary equipment, (d) elevator shaft, (e) guide rails, (f) cab, (g) hoist wire ropes, (h) counter-weight, and (i) safety springs or buffers.

4.2       The sheave, motor and auxiliary equipment are located in a machine room:
4.2.1   The machine room is typically located over the shaft but the motor can be located in the basement; but
4.2.2   Basement location increases power consumption, loading on overhead supports, and wear on ropes;
4.2.3   The room is approximately twice the size of the shaft;
            4.2.4   1 2 additional storeys is required above the top of the beam supporting the elevator shaft.

4.3       Guide rails, cabs, counter-weight, and spring/buffers are installed in the shaft:
4.3.1   Guide rails are placed on each side of the cab;
4.3.2   The hoist wire is attached to the top of the cab at one end, wraps around the sheave, and is attached to the counter-weight at the other end.


5.0        HYDRAULIC ELEVATORS ARE INSTALLED IN LOW-RISE BUILDINGS

5.1       Buildings are typically no higher than 18 m.

5.2       Mechanical components include (a) reservoir, (b) pump, (c) elevator shaft, (d) guide-rails, (e) cab, (f) plunger, and (g) safety springs or buffers.

5.3       The cab is supported by the plunger within the elevator shaft.

5.4       Oil from a reservoir is pumped into the plunger to raise the cab.

5.5       Oil is released from the plunger to lower the cab.

5.6       Plunger may require a hole below the basement floor to a depth equivalent to the travel of the elevator.


FURTHER READING

Mechanical and Electrical Equipment for Buildings, 8th edition, Benjamin Stein, John S. Reynolds, John Wiley & Sons Inc., USA, 1992
Construction Materials & Processes, Don G. Watson, McGrawHill Book Co., USA, 1978;
Architectural Handbook, Alfred M. Kemper, John Wiley & Sons Inc., USA, 1979

18 March 2011

Fire Protection: Physical requirements, Lightning Protection, Detection & Alarm Systems





PAUL HAY Capital Projects


Fire Protection: Physical Requirements, Lightning Protection, Detection & Alarm Systems

Author:          Paul Hay
e-mail:            paul.hay@phcjam.com
profile:           www.linkedin.com/in/phcjam


1.0  INTRODUCTION TO FIRE PROTECTION

1.1        Objectives of fire protection are (a) protection of life, (b) protection of property, and (c) continuation of operation.

1.2       Fire Protection involves (a) fire resistance, (b) lightning protection, (c) fire detection, (d) smoke management and (e) fire suppression.

1.3       Fires can only be sustained if fuel, high temperature and oxygen are all present.

1.4       Structure and contents of a building serve as fuel for fires.

1.5       There are three sources of ignition:
1.5.1   Chemical ignition occurs when volatile substances spontaneously combust under normal temperatures or exposure to open flame;
1.5.2   Electrical ignition occurs when heat is supplied by electrical sources such as arcing or static electricity (e.g. lightning);
1.5.3   Mechanical ignition occurs when heat is produced by friction (e.g. overheating equipment).

1.6       Fires develop in four stages:
1.6.1   At the incipient stage, there is no perception of smoke, flame or appreciable heat;
1.6.2   At the smoldering stage, smoke is visible but there is no flame or appreciable heat;
1.6.3   At the flame stage, appreciable heat is not present;
1.6.4   At the heat stage, smoke, flame and appreciable heat are present.



2.0 THE SITE MUST BE PLANNED TO FACILITATE FIRE PROTECTION

2.1     Unobstructed access must be provided for fire apparatus such as pumpers, ladder trucks and tankers:
2.1.1   Ideally, fire trucks should be able to pull alongside every external wall;
2.1.2   The width of driveways should permit full extension of aerial ladders:

W =     (H - 1.8) Cot α + 1.2                                                                              [2.1]
where,
W =     Distance of far-side of truck from external wall, m
H =      Height to which ladder is to be extended, m
α =       Angle of ladder to roadway (60 deg.> α >80deg.)

2.1.3   Utility poles, wide podiums, outdoor sculptures, fountains, etc. can obstruct the use of aerial ladders;
                        2.1.4   Ordinary fire-fighting apparatus can only extend seven storeys.


2.2       Hydrants should be properly located:
2.2.1   They should be installed 0.6 m - 3 m in from a curb;
2.2.2   They should be located at intersections and be no further than 9 m apart.

2.3       Proper outdoor illumination allows swift location of hydrants.       

2.4       Siamese connections should be within 6m from an hydrant and should be visible and conspicuously marked.

2.5       Proximity to highly flammable surroundings increases the risk of fires:
2.5.1   Firewall construction is a viable option;
2.5.2   Water storage for suppression is another; and
2.5.3   External water sprinklers may be placed adjacent to the building's openings.

2.6       More reliance will have to be made of internal systems when the above are not addressed.

3.0 EGRESS SHOULD BE PLANNED TO FACILITATE FIRE PROTECTION

3.1       Buildings should facilitate evacuation on detection of a fire, until fire-fighters arrive:
3.1.1   At least two exits should be provided;
3.1.2   Means of egress should be provided to theses exits;
3.1.3   Elevators are not means of egress.

3.2       Exit signs must be connected to batteries or emergency power.

3.3       Building Codes specify (a) number of exits required, (b) minimum widths of doorways, (c) minimum width of means of egress, and (d) maximum lengths of means of egress:
3.3.1   Automatic door closures should be used at exit corridors and stairwells;
3.3.2   Distances increase with use of sprinkler systems.

3.4       Building codes also specify the maximum permissible floor area and heights with regard to the building use:
3.4.1   Larger areas need fire walls;
3.4.2   Doors to fire walls may be kept open by door hardware but should close in the event of a fire being detected;
3.4.3   Fire dampers are required in ducts passing through fire walls;
3.4.4   Attention should be paid to vertical openings, as the vertical spread of flame is more important than the horizontal spread.

4.0  BUILDING COMPONENTS MUST BE SELECTED FOR FIRE PROTECTION    

4.1    Building codes specify the fire resistance ratings required for building components depending on the distance from site boundaries or adjacent buildings:
4.1.1   Fire ratings of components are expressed in hours;
4.1.2   Intumescent coatings expand when exposed to fires;
4.1.3   Un-rated and non-combustible materials are allowed in some instances.

4.2     Where sprinkler systems are used, floors should be waterproof and detailed for quick removal of water to facilitate continuity of operation.


5.0 HIGH BUILDINGS HAVE SPECIAL REQUIREMENTS FOR FIRE PROTECTION

5.1     Buildings over 7-storeys high should have electrical generators capable of providing emergency power to (a) fire alarm system, (b) exit and emergency lighting, (c) required ventilation system, (d) fire suppression system, (e) voice communication system and (f) fire elevator.

5.2       High-rise buildings should have at least one elevator connected to emergency power.

5.3       Refuge Areas are required to hold persons unable to evacuate: 
5.3.1   Areas must be able to accommodate all occupants of a floor;
5.3.2   Areas must be adjacent to the escape route; and
5.3.2   Areas must be constructed with materials of high fire resistance ratings.

5.4       Tall structures may have smoke tower stair shafts:
5.4.1   Entrance to stairwell is through a vestibule;
          5.4.2   Pressure differential between (a) stairwell and vestibule, and (b) vestibule and floor area are maintained by separate supply and exhaust fans run on emergency power.

6.0 LIGHTNING PROTECTION IS REQUIRED FOR VULNERABLE BUILDINGS

6.1       The average discharge of lightning is 200 x 106 volts at 30,000 amps:
6.1.1   Cold lightning bolts can shatter and kill but not ignite combustibles;
6.1.2   Hot lightning bolts will ignite combustibles as well as shatter and kill.

6.2       There are four important factors to consider:
6.2.1   Frequency and severity of thunderstorms;
6.2.2   The building's exposure;
6.2.3   Indirect effects, such as losing a water tank; and
6.2.4   The value and nature of the buildings contents.

6.3       Lightning protection involves provision of a continuous metallic path to ground:
6.3.1   Air terminals/Lightning rods shall be spaced no further than 6m on centre around the perimeter of a flat roof, or along the ridge of a pitched roof;
6.3.2   Additional terminals shall be spaced no further than 15 m apart in the middle of large open roofs;
6.3.3   All terminals shall be inter-connected;
6.3.4   The roof perimeter shall be grounded by down leads no further than 30 m apart;
6.3.5   Large metal objects (e.g. VAC units must be bonded to the conductor; and
6.3.6   Smaller metal objects (e.g. roof drains) which are less than 1.8 m from a conductor should also be bonded.



7.0  FIRE DETECTION SYSTEMS GIVE EARLY WARNING OF HAZARD

7.1       Fire alarms operate in three stages: (a) signal initiation, (b) signal processing, and (c) alarm indication.
7.1.1   Signal Initiation can be manual or automatic;
7.1.2   Control equipment, such as Annunciators, process the signal;
7.1.3   An audible, and sometimes visible, alarm is activated.

7.2       Manual fire alarm stations are wall-mounted devices used to activate fire alarms:
7.2.1   Alarm stations and alarms are placed in the path of egress;
7.2.2   Stations can be coded or non-coded:
7.2.2.1            Coded stations make audible alarms that identify the device initiated;
7.2.2.2            Coded stations are recommended when over 10-stations are proposed;
7.2.2.3            Annunciator panels identify where non-coded stations are initiated.

7.3       Smoke Detectors are automatic devices powered by either AC or DC power supply:
7.3.1   Protective wiring or conduits are required if AC power is used;
7.3.2   Smoke and gas inhalation is responsible for 75% of fire-related deaths; and
7.3.3   Fires are responsible for the remaining deaths.

7.4       Five types of smoke detectors are available:
7.4.1   Ionization detectors initiate an alarm when combustion particles are generated at the incipient stage of a fire;
7.4.2   Photo-electric detectors initiate an alarm at the smoldering stage;
7.4.3   Ultra-violet (UV) and Infrared (IR) detectors initiate an alarm at the flame stage:
7.4.3.1            UV detectors are best installed in rooms used to store highly flammable or explosive substances;
7.4.3.2            IR detectors are typically installed in enclosed spaces;
7.4.3.3            The sensitivity of either detector can be adjusted to ignore other sources of UV or IR radiation.
7.4.4   Heat detectors sense temperature and initiate an alarm when the temperature or rise in temperature exceeds a threshold value.

7.5       Care should be exercised in locating smoke detectors to prevent false alarms:
7.5.1   Areas with high humidity or steam (e.g. laundries) should be avoided;
7.5.2   Areas with open flames (e.g. labs) should be avoided;
7.5.3   Areas with exhaust gases (e.g. garages) should be avoided;
7.5.4   Designated smoking areas should be avoided;
7.5.5   Areas that are dust laden should be avoided;
7.5.6   Areas with high air movement (e.g. exit doors) should be avoided.

7.6       Where fires can occur in several stages, different types of detectors can be specified.

7.7       Alarms activate bells, horns, or strobes for swift evacuation:
7.7.1   Coded alarms initially sound an audible code and can be programmed to ring continuously afterwards;
7.7.2   Zone coding is more economical than device coding;
7.7.3   Un-coded alarms ring continuously:
7.7.3.1            Devices can be arranged into zones with annunciator panels;
7.7.3.2            The annunciator will identify the alarm zone.

7.8       Water-flow switches placed on sprinkler piping can initiate a signal to an annunciator.

7.9       Alarm systems are available that can activate smoke removal systems, re-route elevators and activate fire suppression systems.


8.0 FIRE ALARM SYSTEMS SHOULD BE SPECIFIED ACCORDING TO THE BUILDING TYPE

8.1       Small facilities, including residential buildings, should use Local Protective Signaling:
8.1.1   An alarm is only made at the affected premises;
8.1.2   Fire Department is notified manually by occupant, neighbour, or passer-by;

8.2     Public buildings (e.g. schools, government offices, museums, etc.) should use Protective Signaling:
8.2.1   This system is essentially local protective signaling with a direct connection to a municipal fire alarm box;
8.2.2   Alarms are automatically relayed to the Fire Department.

8.3       Private facilities (e.g. shops and offices) which are unoccupied for extended periods of time should use Remote Station Protective Signaling:
8.3.1   This is essentially local protective signaling which automatically dials a pre-selected telephone number;
8.3.2   Alarms are communicated to a remote location that is always manned;
8.3.3   The remote office is responsible for taking further action.  

8.4    Large multi-building facilities (e.g. universities, manufacturing plants, etc.) should use Propriety Protection Signaling:
8.4.1   Alarms are relayed to a central control station on the site manned by personnel associated with the facility;
8.4.2   The control room is generally in a security post or supervisory location such as an Energy Management Department;
8.4.3   Signal transmitted to the control room identifies the exact location or zone within the affected building;
8.4.4   The Fire Department is contacted manually after verification. 





FURTHER READING

            Mechanical and Electrical Equipment for Buildings, 8th edition, Benjamin Stein, John S. Reynolds, John Wiley & Sons Inc., USA, 1992
Construction Materials & Processes, Don G. Watson, McGrawHill Book Co., USA, 1978;
            Ramsey/Sleeper Architectural Graphic Standards, AIA, Robert T. Packard (ed), John Wiley & Sons Inc., USA, 1981;
Architectural Handbook, Alfred M. Kemper, John Wiley & Sons Inc., USA, 1979